Regulatory Reference — United Kingdom

UK EPC Methodology

Non-domestic commercial EPCs in England and Wales are assessed using SBEM — Simplified Building Energy Model. The current version is iSBEM v6.1.e.

Important distinction: domestic vs non-domestic

The June 2025 methodology update that introduced RdSAP 10 applies to domestic EPCs only. It does not apply to commercial buildings.

Non-domestic EPCs continue to use SBEM (iSBEM v6.1.e). Assessors who tell building owners that "the 2025 methodology change improved renewables weighting for commercial buildings" are confusing the two regimes. The relevant change was for residential properties. For commercial buildings, the current SBEM has not had a major update since iSBEM v6.1.e (June 2022), with a minor patch in February 2023.

The government has signalled a non-domestic SBEM methodology review ahead of the 2031 deadline, but no primary DESNZ source confirms a timeline or scope.

Source: UK NCM news log (uk-ncm.org.uk), confirmed 2026-08-25; Propertymark — RdSAP 10 domestic only, June 2025

The assessment tool

SBEM (Simplified Building Energy Model) is the National Calculation Methodology (NCM) for assessing the energy performance of non-domestic buildings in England and Wales. The interface used by assessors is iSBEM.

Current version for England: iSBEM v6.1.e

The last England-specific release was a patch to iSBEM v6.1.e on 9 February 2023. There has been no subsequent England update. Releases in 2024–2026 have been Wales-specific (cSBEM v7.0.d, August 2025) and Scotland-specific (cSBEM v7.0.e, July 2026) only.

For complex buildings, approved Dynamic Simulation Model (DSM) software tools may be used as an alternative.

Download: uk-ncm.org.uk/download.jsp — Royalty-free licence; no pip install required.

NCM news log: uk-ncm.org.uk

— Verified: 25 Aug 2026

Primary guidance

SBEM Technical Manual Authoritative technical reference for the assessment model https://www.uk-ncm.org.uk/download.jsp
Approved Document L2B Building Regulations guidance — existing non-domestic buildings From uk-ncm.org.uk download page
GOV.UK EPC collections page DESNZ guidance hub for non-domestic EPCs https://www.gov.uk/government/collections/energy-performance-certificates
GOV.UK non-domestic MEES landlord guidance Compliance guidance https://www.gov.uk/guidance/non-domestic-private-rented-property-minimum-energy-efficiency-standard-landlord-guidance
Partial EPB regime response (March 2026) Confirms non-domestic EPCs retain carbon metric; domestic-only reform clarified https://gov.uk/government/consultations/reforms-to-the-energy-performance-of-buildings-regime/outcome/

Accreditation

The two primary accreditation bodies for non-domestic EPC assessors in England and Wales:

CIBSE Certification Ltd — operates the Low Carbon Energy Assessor (LCEA) register. The only UKAS-accredited EPC and DEC assessor scheme in the UK.

Elmhurst Energy — major alternative scheme.

Other approved schemes: BRE, Stroma, Quidos, Sterling.

Independence requirement: assessors must not have a commercial interest in the outcome of the rating. Conflicts of interest must be reported to the accreditation scheme.

— Verified: 25 Aug 2026

Key inputs — what drives the rating

SBEM calculates the Building Emission Rate (BER) in kgCO₂/m²/year, compared against a Target Emission Rate (TER) to produce the EPC band. The inputs that matter most, in approximate order of impact:

1. Heating fuel type and system efficiency — gas-heated buildings are significantly disadvantaged under current SBEM carbon factors. SBEM uses 2013-era fuel carbon intensity factors; grid electricity has decarbonised substantially faster than the model credits. For many commercial properties, this is the single most influential variable.

2. Building fabric — insulation values (U-values), glazing, airtightness. Fabric improvements are permanent and reduce baseline energy demand before generation is considered.

3. Lighting systems — LED upgrades are among the most cost-effective interventions per band-improvement point.

4. HVAC systems — heating, cooling, and ventilation system efficiency ratings.

5. On-site generation — wind turbines, solar PV, and (with important limitations) BESS.

6. Building geometry and floor area — total useful floor area determines TER benchmarks by building type.

7. Building use type — SBEM applies different benchmarks for offices, retail, industrial, warehouses, and other categories.

The assessor records: total floor area, construction type, lighting, heating and cooling systems, ventilation, and on-site generation. Data is entered into iSBEM to produce the EPC.

Source: Springer Nature Journal of Building Appraisal — SBEM overview; NZC Consultants — EPC B on gas-heated buildings — Verified: 25 Aug 2026

On-site generation — how each technology is treated

Wind turbines — included

Wind turbines are explicitly included in SBEM inputs. The SBEM methodology requires that "the type and essential aspects of any solar thermal, photovoltaic, combined heat and power or wind turbine" be detailed as part of the assessment.

Where in the calculation: on-site wind generation reduces the net regulated energy consumption of the building, reducing the BER. The mechanism is equivalent to solar PV — generation offsets metered energy consumption from the grid, reducing the carbon figure attributed to the building.

Specific band improvement from a wind turbine installation cannot be stated without a site-specific SBEM assessment against the building's actual baseline parameters.

Source: Springer Nature Journal of Building Appraisal; Complete EPC — SBEM calculations overview — Verified: 25 Aug 2026 (SBEM methodology on wind inclusion is unchanged from 2009)

Solar PV — included

Solar PV reduces net regulated energy consumption in SBEM. The modelled output of the solar array reduces the building's net electricity consumption. As with wind, the specific band improvement depends on system size relative to the building's total floor area and baseline rating.

Important: the June 2025 RdSAP 10 update that improved solar weighting applies to domestic EPCs only. Non-domestic SBEM methodology for solar PV has not changed since iSBEM v6.1.e (June 2022).

Source: EC Eco Energy — on-site generation EPC band improvement, January 2026 — Verified: 25 Aug 2026

BESS — indirect benefit only

Under current SBEM (iSBEM v6.1.e), battery storage does not independently improve a commercial EPC rating the way generation does. SBEM credits generation at the point of production, not consumption. BESS enables self-consumption optimisation and grid export management, but SBEM does not currently give direct credit for storage capacity as a standalone metric.

BESS delivers real operational and commercial value to building owners through energy cost savings and grid export revenue. That value does not flow directly into the EPC rating under current methodology.

No England SBEM update addressing BESS is announced or scheduled as at 2026-08-25. The partial EPB regime response (March 2026) confirms non-domestic EPCs will retain the carbon (Environmental Impact Rating) metric — not the domestic four-headline-metric structure (energy costs, fabric, smart readiness, heating efficiency). The smart readiness and BESS scoring changes apply to domestic EPCs only.

Source: Partial EPB regime response, MHCLG/DESNZ, March 2026 — Verified: 25 Aug 2026

Understanding what this means for your building → Owner pathway

Verified: 25 Aug 2026

The RdSAP 10 / domestic distinction is confirmed from NCM news log and DESNZ partial EPB response.